Products
GDI Solutions provide the best technology and services in environmental and safety measurements.

FGD FlameSpec UV/IR Flame detector
FlameSpec-UV-IR flame detector providing ultra-fast response, high performance and reliable detection of a large variety of fires including hydrocarbon fires (visible and nonvisible), as well as Hydrogen fires. The detector addresses slow growing fires as well as fast eruptions of fire using improved UV IR technology. The detector operates in all weather and light conditions.
Features and Benefits
- High immunity to false alarm
- Ultra-fast detection mode – detection within 5 milliseconds for fireballs or explosions
- Hydrogen and Hydrocarbon flame detection
- High sensitivity mode – From up to 100ft.(30m) to 1ft2(0.1m2) n-heptane pan fire
- Data/Event logger – alarm error, and other relevant events are logged to non-volatile memory
- Built-in-Test(BIT) – Automatic and manual internal self-test of window cleanliness and the overall operation of the detector
- Window heater to avoid condensation and icing
- Stainless Steel Tilt mounting bracket can be connected either above or below the detector
- Individual warning levels for UV and IR
- ATEX/IECEx/FM/DNV certifications
- SIL2 certified(Pending)
Product Specification
Category | Item | Description |
---|---|---|
Fire Detection | Detection time and distance |
5ms for fast fire burst or explosion 1s for 1 ft2 (0.1m2) pan fire at 0–50 ft. (0–15m) <2s for 1 ft2 (0.1m2) pan fire at 50–100 ft. (15–30m) |
Field of view (IR detection) | 90° Horizontal, 75° Vertical | |
Time Delay | 0-30 seconds | |
Built in Test | Automatic and Manual | |
Electrical specifications | Operating Voltage | 24 VDC nominal (18-32 VDC) |
Current Consumption |
Standby: 120mA Maximum: 180mA all systems in operation (including window heater) |
|
Electrical Entries | 2x cable and conduit entries 3/4″ 14NPT or M25x1.5 | |
Wiring | 12-20AWG (2.5-0.35mm2) | |
Outputs | Relays |
SPST volt-free contacts rated 2A at 30 VDC Alarm – normally open; Fault – normally closed |
0-20mA (stepped) current output |
3 wire and 4 wire (isolated) configurations (sink and source) HART® rev 7.0 (option available) |
|
Indication | Tri-color LED (Green, Yellow, Red) | |
Modbus | RTU compatible on RS-485 | |
Mechanical Specifications | Size | 5.51 x 3.54 x 3.54″ (140x90x90mm) |
Weight |
Detector (Stainless Steel 316) : 6.6 lbs. (3.0 kg) Tilt mount (Stainless Steel 316) : 3.3 lbs. (1.5 kg) |
|
Environmental Specifications | Temperature range |
Operating : -67°F to +167°F (-55°C to +75°C) Option : -67°F to +185°F (-55°C to +85°C) Storage : -67°F to +185°F (-55°C to +85°C) |
Humidity | Up to 99% (RH), non-condensing | |
Ingress Protection | IP66 & 68(2m, 24hr); NEMA 4X & 6P | |
Approvals | ATEX |
ATEX : II 2 G D Ex db IIC T5 Gb or Ex db eb IIC T5 Gb and Ex tb IIIC T95°C Db -55°C < Ta < 75°C Ex db IIC T4 Gb or Ex db eb IIC T4 Gb and Ex tb IIIC T105°C Db -55°C < Ta < 85°C |
IECEx, INMETRO & PESO |
Ex db IIC T5 Gb -50°C≤Ta≤75°C Ex db IIC T4 Gb -50°C≤Ta≤85°C |
|
FMus & FMc |
Class I, Div. 1, Groups B, C & D; T4 Class I, Zone 1, AEx/Ex db IIC T4 Gb T4 -50°C≤Ta≤85°C T5 -50°C≤Ta≤75°C |
|
EAC CU TR |
1Ex d IIC T5 Gb or 1Ex de IIC T5 Gb and Ex tb IIIC T95°C Db -55°C≤Ta≤75°C 1Ex d IIC T4 Gb or 1Ex de IIC T4 Gb and Ex tb IIIC T105°C Db -55°C≤Ta≤85°C |
|
Performance |
ANSI FM 3260 EN 54-10 |
|
Funcional safety | Complies to SIL2, per IEC 61508 (option available) | |
Accesories |
Stainless steel weather cover Flame simulator, model FLS-FSIM-UVIR-KIT 2" & 3" pole mount adapter Airshield for areas with high airborne contamination |
|
Warranty | 5 years |